Features
Ironclad® extra thick tubular plates as per exclusive Exide design ensuring durability, resistance to corrosion and inbuilt margins for high ambient temperature. Very long life — Suitable for frequent and long power cuts (800 to 1000 cycles at deep discharge) with quick recharge adaptability.
Spines cast with Torr Tubular technology in HADI machine at 100 bar. Low maintenance characteristics with high acid volume per ampere-hour.
Tower type strong and rugged polypropylene container and heat-sealed tamper proof lids with rope handle for easy lifting
arrangement.
Low self-discharge and Resistance to abuse — Can withstand overcharge better.
PE pocket type separators Substantial savings in floor area.
Micro-porous ceramic vent plugs makes it more environment friendly. Conforms to Is 13369 — 1992.
Resistance to corrosion and high ambient temperature.    
Applications
Domestic Inverters    
Technical Specifications

Model

Capacity at 270C when discharged at C20 upto 1.75 vpc (1.280 sp.gr)

Dimension (+/-3mm)

Weight
(Kg +/-5%)

Volume of Electrolyte
(1.220 Sp. Gr) Liters/Cell

Initial charge Minimum AH input (AH)

Initial Charge of Constant Current (A)

Constant Potential Limiting Current (Amps)

Trickle Charge
(Current in mA)



Length



Width



Height*



Dry



Filied
Start (upto 2.36 vpc) Finish (upto 2.75 vpc)


Min.



Max.
INVA GOLD500

150 Ah

500

187

430

36.56

62.55

3.55

540

14.4

7.2

30

120

480

Initial Charging Instructions
Fill in with electrolyte of specific gravity of 1.220 ± 0.005 at 27°C.
Leave the battery idle for 10 hours after acid filling and before commencing initial charging.
In order to reduce the charging time, the following routine may be adopted. for INVAGOLD500, the initial charging current may be 14.4A upto 2.36 vpc followed by 7.2A upto 2.75 vpc
Temperature not to exceed 50°C. Rest to be provided if temperature exceeds 50°C till temperature comes down to ambient temperature.
Conditions of fully charged
 
3 consecutive hourly readings of specific gravity and voltage become constant.
Top of charge voltage will e around 16.2V – 16.5V.
All cells should gas freely.
Minimum Ah has been given.
Specified gravity of fully charged condition - 1.250 +/ - 0.005 at 27ºC
Normal Recharge
Recharging through Inverter at constant potential mode of 14.4 Volt with limited current as specified. After battery potential reaches 14.4 Volts, the battery should continue in trickle charge mode at constant potential of 13.8 Volts.
In case of bench recharging, the charging rate should be the same as initial charging till 16.5 Volts.
INVA GOLD is a product of ISO 9001 AND ISO 14001 certified factories
Statutory Warning
All batteries contain lead, which is harmful for humans and environment. As per statutory requirements, the used battery must be returned to the authorized dealer, manufacturer or at the designated collection centres.